Locating Inadvertently Partially Closed Valves in Water Distribution Systems - INRAE - Institut national de recherche pour l’agriculture, l’alimentation et l’environnement Accéder directement au contenu
Article Dans Une Revue Journal of Water Resources Planning and Management Année : 2018

Locating Inadvertently Partially Closed Valves in Water Distribution Systems

Localisation de vannes accidentellement partiellement fermées dans un réseau de distribution d'eau

Résumé

The reliability of a water distribution system is highly dependent on the management of its pipeline network. A pipe or a portion of the network can be isolated for inspection, maintenance, and replacement by the installation of isolation valves along the pipelines. However, the presence of isolation valves may cause a large discrepancy in the hydraulic behavior between the real system and results from a simulation model if the statuses of some of the valves in the system are unknown. Possible problems related to these valves are missing valves in the model due to poor or nonexistent documentation, errors in data transfer, or valve mechanical failure. This paper introduces an innovative methodology for the identification of unknown partially/fully closed valves in a water distribution network. An optimization problem is formulated for the unknown valve issue and solved by application of three sequentially applied methods, which include a local sensitivity analysis, an application of genetic algorithms (GAs), and an application of the Levenberg-Marquardt algorithm. In the first method, the sensitivity of the flow rates and nodal heads at measurement locations with respect to the change in the minor losses of the valves is computed. This computation is used to identify the valves that are unable to be localized by the measurement data. The second method applies a genetic algorithm combined with an extended period simulation in order to preliminarily identify the locations of the partially/fully closed valves and their setting values, i.e., the degree of opening of the valve. Finally, the application of the Levenberg-Marquardt (LM) algorithm was implemented to correct the results from the GA model. Results and discussions from two case studies show that the proposed methodologies can solve real-world problems.
Fichier non déposé

Dates et versions

hal-02607513 , version 1 (16-05-2020)

Identifiants

Citer

Nhu Cuong Do, Angus Simpson, Jochen Deuerlein, Olivier Piller. Locating Inadvertently Partially Closed Valves in Water Distribution Systems. Journal of Water Resources Planning and Management, 2018, 144 (8), 04018039, 14 p. ⟨10.1061/(ASCE)WR.1943-5452.0000958⟩. ⟨hal-02607513⟩
61 Consultations
0 Téléchargements

Altmetric

Partager

Gmail Facebook X LinkedIn More